Overview
NFPA 72 2016 Supervision requirements state that pathways between the remote call stations and the master control station shall be monitored for integrity. To meet these requirements:
  • Each 2400 Series Call Box, Command Center, and outside phone line connect directly into the RATH Supervisor Board (2500__-SPRVSR). The 2500-__SPRVSR has a Communications Failure relay output that can be connected to an addressable fire alarm module or fire control panel.
  • Each IP Call Box, along with the Command Center, has a unique IP address that the 2500-VOIPM "pings" every 10 minutes to ensure connection. If power supervision is needed, an additional purchase of the UPS Monitor (2500-UPSMONITOR), which includes a Power Failure relay output, is required.
Play
AVIRE App (EN)
2500-VOIPM-IP-Supervisor
2500-VOIPM IP Supervisor

The RATH IP Supervisor allows supervision for up to 200 RATH IP endpoints (Phones and Command Center). The default system check is once every 10 minutes, but the time frame is adjustable. If the Supervisor does not detect one of the programmed IP endpoints or the network goes down, it will provide a contact closure alarm. Device includes Supervisor, relay output, and network cable.

Dimensions:  11-1/2″ H x 10″ W x 5″ D

Code Compliance:  UL 61010-1

Current Draw:  270mA

Output: (2) Form 1C SPDT switches, (1) NO and (1) NC. Rated 277vac at 20A
Ethernet: (2) 10 Base-T or 100 Base-T, 8-pin RJ45 connection
Network: Ethernet IPv4
• Requires static IP addresses for all components
• Supports web browser: HTTP/HTTPS, XML, Modbus/TCP & SNMP protocols
LED indicators: Green (power on) Yellow (network)
Temperature range:  -40°F – 150°F

Additional Features:
• Non-volatile memory
• Electromagnetic compliance: IEC CISPR 22, 24. FCC 47CFR15 (Class B)
Power Requirements:
• 120vac from a backed up power source or use RATH model RP7700104
Mounting: Wall mount enclosure with door

Warranty: 2 years






2500-UPSMONITOR
2500-UPSMONITOR

Dimensions:  5-1/4″ H x 3-1/8″ W x 2-5/8″ D

Power Requirements:
• 24vdc @ 28mA / 24vac @ 69mA
• 120vac @ 45mA / 230vac @ 36mA per module position

Polarized Coil Input(s): DC control inputs only

Energized Indicator: One red LED per module position

Contact Ratings:
• Resistive load: 7A @ 30vdc, 10A @ 125vac, 7A @ 250vac
• Inductive load: .25 HP 125/250vac (N.C.), .33HP 125/250vac (N.O.)

Contact Construction:  Dry form “C” DPDT per module position

Ambient Temperature:
• 32ºF to 120ºF (0°C to 49°C) @ 93% RH (@32°C)
• Non-Condensing / Non-Freezing

“/T” Versions:
• 3.5″ wide, low profile snap track provided with mounting screws

“/C” Versions:
Backbox: 18ga CRS, plated with 1/2″ conduit knockouts top and bottom
Cover Material: MR-101, MR-201: plastic ABS 94V-0 (“/C” Grey, “/C/R” Red) MR-104, MR-204: CRS 18ga (“/C” Grey, “/C/R” Red)

Approvals:

“T” versions: UL Recognized Component (UL864, UOXX2)File #S3403, CSFM File #7300-1004:106 “C” versions: UL Listed (UL864, UOXX), CUL Listed (UL864, UOXX7) File #S3403, CSFM File #7300-1004:101, MEA File #73-92-E Vol.14 (MR-101, MR-104), Vol. 16 (MR-201, MR-204) “C/R” versions: UL Listed (UL864, UOXX), CUL Listed (UL864, UOXX7) File #S3403, CSFM File #7300-1004:101, MEA File #73-92-E Vol. 22

Warranty: 2 years