Find your region

Avire-Logo-Group

For countries not listed, see the Global site.

Note: Some products are available only in certain regions. Contact us regarding local availability.

Command-Center-Supervision

Command Center 360° Supervision

Only available in
USA
COMPLIANT WITH
NFPA 72®
Overview
NFPA 72 2016 360° Supervision requirements state that pathways between the remote call stations and the master control station shall be monitored for integrity. To meet these requirements:
  • Each 2400 Series Call Box, Command Center, and outside phone line connect directly into the RATH Supervisor Board (2500__-SPRVSR). The 2500-__SPRVSR has a Communications Failure relay output that can be connected to an addressable fire alarm module or fire control panel
  • If power supervision is needed, an additional purchase of the UPS Monitor (2500-UPSMONITOR), which includes a Power Failure relay output, is required.
2500-__SPRVSR
2500-__SPRVSR
Available in 12, 16, 28, 36, 56, 76, 96, or 116 Zone
• Includes 2500-UPSMONITOR
• To order without the UPS Monitor, add an “N” to the end of the model number (ex: 2500-12SPRVSRN)

Specifications:
• Supervisor monitors remote Call Boxes and telephone lines
• Provides a relay output when it does not detect a component of the system

Connections: RJ11 connections to each Call Box and phone line, punch down terminal connections to Distribution Module

Power Requirements: 12vdc (includes UL listed transformer that plugs into a 120vac backed up source or use RATH model RP7700104 or RP7701500

Mounting: Wall mounted swing out bracket

Warranty: 2 years




















2500-UPSMONITOR
2500-UPSMONITOR
5-1/4″ H x 3-1/8″ W x 2-5/8″ D

Power Requirements:
• 24vdc @ 28mA / 24vac @ 69mA
• 120vac @ 45mA / 230vac @ 36mA per module position

Polarized Coil Input(s):  DC control inputs only

Energized Indicator: One red LED per module position

Contact Ratings:
• Resistive load: 7A @ 30vdc, 10A @ 125vac, 7A @ 250vac
• Inductive load: .25 HP 125/250vac (N.C.), .33HP 125/250vac (N.O.)

Contact Construction: Dry form “C” DPDT per module position

Ambient Temperature:
• 32ºF to 120ºF (0°C to 49°C) @ 93% RH (@32°C)
• Non-Condensing / Non-Freezing

“/T” Versions: 3.5″ wide, low profile snap track provided with mounting screws

“/C” Versions:
• Backbox: 18ga CRS, plated with 1/2″ conduit knockouts top and bottom
• Cover Material: MR-101, MR-201: plastic ABS 94V-0 (“/C” Grey, “/C/R” Red) MR-104, MR-204: CRS 18ga (“/C” Grey, “/C/R” Red)

Approvals:
• “T” versions: UL Recognized Component (UL864, UOXX2)File #S3403, CSFM File #7300-1004:106 “C” versions: UL Listed (UL864, UOXX), CUL Listed (UL864, UOXX7) File #S3403, CSFM File #7300-1004:101, MEA File #73-92-E Vol.14 (MR-101, MR-104), Vol. 16 (MR-201, MR-204) “C/R” versions: UL Listed (UL864, UOXX), CUL Listed (UL864, UOXX7) File #S3403, CSFM File #7300-1004:101, MEA File #73-92-E Vol. 22

Files and Resources

Command System Supervisor 2500 SPRVSR Datasheet
Datasheets
Download
Supervisor Board RP8500SPRVSR Manual
UPS Monitor RP8500UPSM-2500 Installation Manual
Install Guides
Download
Relay Control Card RP8500LUPSM-2500LUPSM Installation Manual
Install Guides
Download

Specifiers' Corner

The Specifiers’ Corner is designed to provide Architects, Engineers, Contractors, Fire Marshals, Building Code Officials, Inspectors, AHJs, and end users with the essential information that may be needed for a project: Submittal Documents, Manuals/Wiring Diagrams, Data Sheets,CAD and Code Requirements

Contact info

You also can contact us through our phone number, our email address, and we’ll get back to you

rath-janus@avire-global.com
+800-451-1460
Office Locations

We believe that ongoing education is paramount to your professional development.

As the code and training experts, our website offers all the documentation and educational resources needed to assist you in making the right decisions.